Detailed Buying Lead Description

Dear Sir,

We require LFO fired boiler for steam generation. The details are as follows:

1 Unit         LFO fired boiler for steam generation

An independent light fuel oil fired boiler will be used during the start-up of the power plant, for heating the heavy fuel system during outages and when the main exhaust gas boilers are not in use.

The auxiliary boiler unit includes:

Evaporator section

LFO burner

Gas burner

LFO pump

Combustion air fan

Steam pressure gauge

Pressure switches

Temperature switches

Level control device

Main closing valve for steam

Non-return valve at steam outlet

Safety valves

Local control panel

Interconnection pipes, flanges and gaskets

Feed water pump

Capacity at boiler outlet at Stated Ambient Conditions as specified in section and clean heat exchanger surfaces:

Steam generation                       5 t/h saturated steam -at feed water temperature 90oC

Working steam pressure      7 bar(a)