| Is developed by independent By comking in the basis of similar products at home and abroad, is mainly used in power plants in 12 |
Is developed by independent By comking in the basis of similar products at home and abroad, is mainly used in power plants in 12
Is developed by independent By comking in the basis of similar products at home and abroad, is mainly used in power plants in 12kV power system, substations and distribution system control and protection; is particularly well suited to the requirements under the rated operating current operation or more frequently breaking and closing of places of short-circuit current, with very good performance.Adaptive counter-based products for KYN28, XGN2, GG1A and so on.
Technical parameters
Name | Units | parameters | ||||
Rated voltage | kV | 12 | ||||
Rated insulation level | Rated short-term tolerance to voltage | kV | 42 | |||
PeakLightning Impulse Voltage tolerance | kV | 75 | ||||
Rated Frequency | Hz | 50 | ||||
Secondary circuit voltage frequency tolerance | V | 2000 | ||||
Rated Current | A | 630 | 1250 | 1600 | ||
4sRated short-term whithstand current | kA | 25 | 25 | 31.5 | 31.5 | |
Rated peak whithstand current | kA | 63 | 63 | 80 | 80 | |
Rated short-circuit breaking current | kA | 25 | 25 | 31.5 | 31.5 | |
Rated short-circuit closing current | kA | 63 | 63 | 80 | 80 | |
Rated cable charging breaking current | A | 25 | ||||
Rated capacitor current portfolio Closing | kA | 12.5 | ||||
Rated a single / back-to-back capacitor bank breaking current | A | 630/400 | ||||
Operation order |
| -0.3s--180s- | ||||
Mechanical life | 20000 | |||||
Breaking number of rated current (electrical life) | 20000 | |||||
number of Rated short-circuit current breaking | 50 | |||||
clearance between open gap | mm | 11±1 | ||||
overtravel | mm | 3.5±1 | ||||
Average closing speed | m/s | 0.50.8 | ||||
Average opening speed | m/s | 0.91.2 | ||||
closing time | ms | 3570 | ||||
opening time | ms | 3050 | ||||
Arcing time | ms | ≤15 | ||||
Contact closing bounce time | ms | ≤2 | ||||
Three-phase contact line at different periods of gate
| ms | ≤2 | ||||
Dynamic and static contact allowed to wear a total thickness
| mm | 3 | ||||
| Business Type: | Manufacturer |
| Product/Service (We Sell): | Vacuum circuit-breaker,voltage vacuum load switch,circuit breaker switchgear,earthed neutral resistance,full insulation and fully sealed sf6 switchgear se |
| Brands: | comking |
| Number of Employees: | 101 - 500 People |
| Management Certification: | ISO 9000/9001/9004/19011: 2000 |