Coal Chain-Grate Power Station Boiler

Browse similar products from this supplier
Place of Origin: China
Usage: Power Station

Supplier Details

Wuxi Taihu Boiler Co., Ltd.

[ Jiangsu, China (Mainland) ]
  • Business Type:Manufacturer
  • Product/Services:Class A boilers
  • Online Showroom: 25 products
View this Supplier's Website >>
Gold Supplier [ 4th Year] Verified Supplier
  • Product Details
  • Company Profile
  • Place of Origin: China
  • Usage: Power Station

Main criterion for coal chain-grate boiler is WB-35 / 3.82-M

Technical parameters:
1) Rated evaporation: 35MT/h
2) Rated vapor pressure: 3.82MPa
3) Rated vapor temperature: 450oC
4) Vapor working pressure in the boiler: 4.21MPa
5) Feeding water temperature: 150oC
6) Feeding water pressure: 4.61MPa
7) Hot air temperature: 141oC
8) Continuous waste discharging rate: 2%
9) The designed efficiency of the boiler set: 80%

Applicable fuel specifications:
1) Designed fuel: lean coal (soft coal is also available) 
2) Cy: 58.21%
3) Hy: 2.91%
4) Oy: 2.51%
5) Ny: 1.64%
6) Sy: 0.68%
7) Ay: 26.57%   
8) Wy: 7.48%
9) Vr: 16 - 18% 
10) QyDW: 21,094kJ/kg (5,038kcal/kg)
11) T1: >1,200oC
12) T2: ≥1,280oC
13) T3: ≥400
14) Calculated fuel consumption: Bj=5,053kg/h
15) Max. coal grain dimensions: 40mm, 0 - 3mm<30%, 0 - 0.1mm<2.5%

This boiler is a medium-pressure single-drum natural cycle boiler laid in ∩-shape. It is installed with strobe coal scuttle and veering squama non-coal-leakage chain-grate burning equipment. The hearth is surrounded with water-cooling wall pipe, and the exit of the hearth is installed with loose residue congealed pipe. The horizontal flue is equipped with vertical convection super-heater. It is divided into high temperature and low temperature sections according to the steam flowing directions. The screwed pipe attemperator is used to regulate steam temperature, which is in the center of high temperature and low temperature section super-heater. The direct well of the boiler tail is installed with single steel tube coal economizer and pipe air pre-heater. The residue discharging equipment is with Martin tap tole with disc extruder available. The entire water capacity of the boiler is 30MT.

Send your message to this supplier

Coal Chain-Grate Power Station Boiler
Main criterion for coal chain-grate boiler is WB-35 / 3.82-M
Double-Drum Bulk Steam Boiler
Type: SHL35-1.6-AII bulk water pipe steam boiler
Bulk Hot Water Boiler
Type: DHL29-1.6 / 130 / 70-AII bulk hot water boiler
Double-Drum Bulk Steam Boiler
Type: SHL35-1.6-AII bulk water pipe steam boiler