No. | Item | Unit | Data | ||||
1 | Rated voltage | kV | 40.5/35 | ||||
2 | Rated current | A | 1600 | 2000 | |||
3 | Rated short circuit breaking current |
kA
| 20 | 25 | 31.5 | ||
4 | Rated short circuit breaking current (peak value) | 50
| 63 | 80 | |||
5 | rated short time withstand current | 20 | 25 | 31.5 | |||
6 | Rated peak value withstand current | 50 | 63 | 80 | |||
7 | Rated short-circuit duration | s | 4 | ||||
8 | Rated insulation level | Power frequency withstand voltage | Dry type |
kV | 95 | ||
Wet type | 80 | ||||||
Impulse withstand voltage | 185 | ||||||
9 | Rated sequence of operations |
| O-0.3s-CO-180s-CO | ||||
10 | Mechanical life | Time | 10000 | ||||
11 | Breaking times for rated short circuit current | Time | 20 | ||||
12 | Full breaking time(to match spring operating device) | ms | ≤80 | ||||