LCD display Online UPS 6kVA 10kVA Double Conversion UPS for Medical

  • 1-9 Pieces
    $346.81
  • 10-99 Pieces
    $339.81
  • >=100 Pieces
    $328.72
Quantity:
- + Pieces available
0piecesselected, US $in total
View Details
Shipping fee:
Depends on the order quantity.
Lead Time:
7 day(s) after payment received
Customization:
Customized logo (Min. Order: 10 Pieces)
Customized packaging (Min. Order: 100 Pieces)
Contact Supplier
Samples - $339.81 /Piece, 1 Piece (Min. Order): Buy Samples
Loading... Add To Cart
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
CPSY
Model Number:
HP1106H
Phase:
Single Phase
Protection:
Overvoltage
Weight:
20.901KGS
Output Voltage:
200/208/220/230/240VAC
Type:
On-line
Application:
Security / Monitoring / Alarm
Battery Type:
Sealed Lead Acid Battery
Color:
Black
Certification:
CE/ISO/TLC/COC
Wave Form:
Pure Sine Wave Online Ups
Input voltage:
110-300Vac
Display:
LED/LCD
Full protection:
Yes
True double-conversion:
yes
Maintenance bypass:
Available
Battery:
Inside or external connect

Packaging & Delivery

Selling Units:
Single item
Single package size: 
60X40X60 cm
Single gross weight:
20.901 kg
Package Type:
small ups in box with pallet, while the big ups package in wooden crast.
Lead Time :
Quantity(Piece) 1 - 2 3 - 10 11 - 100 >100
Est. Time(days) 7 10 15 To be negotiated
MASS_APP4_482_BEGIN

MASS_APP4_482_END
Product Description

 LCD display  Online UPS 6kVA 10kVA Double Conversion UPS for Medical

 

Main Features

1) True double-version online UPS

2) DSP technology guarantees high performance

3) Output power factor 0.8

4) Standard backup UPS and long backup UPS in one intergrated unit

5) Adujstable battery number from 16pcs to 20pcs

6) Adjustable charging current via software(0.5A-0.6A)

7) Wide put voltage range(110VAC-300VAC)

8) Active iput power factor correction 0.99

9) 50Hz/60Hz frequency converter mode

10) Emergency power off function

11) 3-stage extendable charging design for optimized battery performance

12) Maintenance bypass available

13) SNMP/USB/RS-232 communication

 

Technical Specification

ModelHP1106B(H)HP1110B(H)
Capacity6000VA/4800W10000VA/8000W
Phase1 Phase in / 1 phase out
Input
Voltage RangeLow Line Transfer110 VAC±3% at 50% Load 176VAC±3% at 100%Load
Low Line Comeback120 VAC±3% at 50% Load 186VAC±3% at 100%Load
High Line Loss300 VAC ±3%
High Line Comeback290 VAC ±3%
Frequency Range46Hz~54Hz or 56Hz~64Hz
Power Factor≥0.99 @100% Load
Output
Output voltage200/208/220/203/240VAC
AC Voltage Regulation±1%
Frequency Range(Synchronized Range)46Hz~54Hz @ 50Hz system ; 56Hz~64Hz @ 60Hz system
Frequency Range(Batt. Mode)50 Hz± 0.1Hz or 60 Hz± 0.1Hz
Current Crest Ratio3:1(max.)
Harmonic Distortion≤3% THD(Linear Load),≤6%THD(Non-linear Load)
Transfer timeBypass to Inverter
(Line mode)
0 ms
Inverter to Bypass
(Line mode)
0 ms
Waveform(Batt. Mode)Pure Sinewave
Efficiency(Peak)
Line Mode90%
Battery Mode89%
Battery
Standard ModelBattery Type12V/7Ah12V/9Ah
Battery Number16pcs16pcs
Typical Regarge time9 hours recover to 90% capacity
Charging currentDefult:1.0A ±10%,Max.:2.0A±10%
Float Charging Voltage218.4 VDC ±1%(Based on 16 pcs batteries)
Long-run ModelBattery type Depending on applications
Battery Number16-20 pcs(adjustable)
Charging currentDefult:4.0A ±10
Float Charging Voltage218.4 VDC ±1%(Based on 16 pcs batteries)
Indicatiors
LED PanelUPS Status,Load level,Battery level,and Fault conditions
Alarm
Battery ModeSounding every 4 seconds
Low BatterySounding every seconds
OverloadSounding twice every  seconds
FaultContinously sounding
Physical
Standard ModelD x W x H(mm)530 x 250 x 608530 x 250 x 608
Net Weight(kg)6070
Long-run ModelD x W x H(mm)515 x 245 x 455515 x 245 x 455
Net Weight(kg)2030
Environment
Operation Humidity0-95% RH @ 0-40℃(non-condensing)
Noise LevelLess than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter 
Management     
Smart RS-232Supports Windows@ 2000/2003/XP/Vista/2008,
Windows@7,Linux,Unix and MAC
Optional SNMPPower management from SNMP manager and web browser

 

 

 

 

Product Images

 

Contact Us

 

Company Information

 

 

 

Certificate:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Packaging & Shipping

 

Our Services

 

FAQ

 

How to choose the right UPS? 
1. Understand specifications of all UPS.
2. Consider the requirements of power quality.
3. Understand the current capacity of UPS and consider the future expansion.
4. Choose reputed brands and manufacturers.
5. Choose UPS based on your requirements. 

 

What are the important items you should evaluate when buying a UPS? 
1. UPS reliability and stability.
2. The excellent engineers and the ability of products creation.
3. High efficiency and low noise.

 

What is the impact of different output waveforms? 
There are three major types of loads, Resistive load (Lamps), SPS load (PC power supply) & Conductive

Load (Motors). All the types of load can be used with Pure Sinewave. However, only Resistive and SPS loads can be used with Modified Sinewave.

 

 

 